NEC 314.16NEC 2026

Free NEC 314.16 Box Fill Calculator

Calculate box fill to NEC 314.16 in seconds. Enter your conductors, devices, and equipment grounding conductors to verify the box isn't overfilled before you land wires. Overfilled boxes cause overheating, damaged insulation, and failed inspections — the demo below shows exactly how the full tool breaks down every volume allowance.

Why box fill matters

  • NEC 314.16 limits the number and size of conductors, devices, and clamps allowed in a box.
  • Each item counts as a volume allowance based on the largest conductor in the box.
  • Exceeding the box's volume capacity risks overheating, insulation damage, and rejected inspections.
BOX FILL CALCULATORDEMO
BOX TYPE (NEC 314.16)
4" Square × 1-1/2" Deep — 21 in³
CONDUCTOR
2
BOX-MOUNTED ITEMS
Device
1
EGC
1
47.6% BOX
NEC LIMIT 100%
PASS
PASS

Total fill of 10.00 in³ fits within the box capacity of 21 in³ (47.6% used).

NEC 314.16 — Box Fill Calculation

FILL BREAKDOWN
2 × 14 AWG = 4.00 in³
1 × device (2× largest wire) = 4.00 in³
1 × EGC (1× largest EGC) = 2.00 in³
TOTAL FILL10.00 in³
REMAINING11.00 in³

Run the full NEC 2026 box fill calculator

Enter multiple conductor groups and any box type, then pair it with the conduit fill calculator, the safety protocols, and the full electrical academy.

OPEN THE CALCULATOR

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.