Pocket Reference

The tables, formulas, and code limits electricians reach for every day — organized by topic.

REFERENCE TOPIC

Ampacity

Copper and aluminum ampacities, ambient correction, bundling adjustment, and circular mils.

Copper conductor ampacities

310.16
Size60°C75°C90°C
14152025
12202530
10303540
8405055
6556575
4708595
385100115
295115130
1110130145
1/0125150170
2/0145175195
3/0165200225
4/0195230260
250215255290
300240285320
350260310350
400280335380
500320380430
600350420475
750400475535
1000455545615

Not more than three current-carrying conductors in a raceway or cable, 30°C ambient. Amperes.

Aluminum conductor ampacities

310.16
Size60°C75°C90°C
14———
12152025
10253035
8304045
6405055
4556575
3657585
27590100
185100115
1/0100120135
2/0115135150
3/0130155175
4/0150180205
250170205230
300195230260
350210250280
400225270305
500260310350
600285340385
750320385435
1000375445500

Same basis as the copper table. Small aluminum conductors are uncommon below 12 AWG.

Ambient temperature correction

310.15(B)(1)
Ambient temperature60°C75°C90°C
21–25°C (70–77°F)1.081.051.04
26–30°C (78–86°F)1.001.001.00
31–35°C (87–95°F)0.910.940.96
36–40°C (96–104°F)0.820.880.91
41–45°C (105–113°F)0.710.820.87
46–50°C (114–122°F)0.580.750.82
51–55°C (123–131°F)0.410.670.76
56–60°C (132–140°F)—0.580.71
61–65°C (141–149°F)—0.470.65
66–70°C (150–158°F)—0.330.58
71–75°C (159–167°F)——0.50
76–80°C (168–176°F)——0.41

Multiply the table ampacity by the factor for the ambient temperature the conductor will actually see.

Adjustment for bundled conductors

310.15(C)(1)
Current-carrying conductorsPercent of table valueMultiplier
4 to 680%0.80
7 to 970%0.70
10 to 2050%0.50
21 to 3045%0.45
31 to 4040%0.40
41 and above35%0.35

Apply after temperature correction whenever more than three current-carrying conductors share a raceway or cable.

Circular mils by size

Chapter 9, Table 8
SizeCircular mils
144,107
126,530
1010,380
816,510
626,240
441,740
352,620
266,360
183,690
1/0105,600
2/0133,100
3/0167,800
4/0211,600
250250,000
300300,000
350350,000
400400,000
500500,000
600—
750—
1000—

Used for voltage drop, resistance, and conductor area calculations.

Sizing rules

  • Ampacity comes from the table, then every applicable correction and adjustment factor is applied.
  • Terminations limit the usable column: 60°C for circuits 100 A or less unless the terminals are listed otherwise, 75°C for most equipment rated over 100 A.
  • Small conductors have a hard ceiling regardless of the table: 15 A for 14 AWG, 20 A for 12 AWG, and 30 A for 10 AWG copper.
  • The neutral is not a current-carrying conductor on a balanced three-phase wye circuit.
  • Conductors in a wet location need a wet-rated insulation, which changes the temperature column you may use.
  • Never size a conductor from the 90°C column just because the insulation allows it. The termination still governs.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.