The tables, formulas, and code limits electricians reach for every day — organized by topic.
REFERENCE TOPIC
Copper and aluminum ampacities, ambient correction, bundling adjustment, and circular mils.
| Size | 60°C | 75°C | 90°C |
|---|---|---|---|
| 14 | 15 | 20 | 25 |
| 12 | 20 | 25 | 30 |
| 10 | 30 | 35 | 40 |
| 8 | 40 | 50 | 55 |
| 6 | 55 | 65 | 75 |
| 4 | 70 | 85 | 95 |
| 3 | 85 | 100 | 115 |
| 2 | 95 | 115 | 130 |
| 1 | 110 | 130 | 145 |
| 1/0 | 125 | 150 | 170 |
| 2/0 | 145 | 175 | 195 |
| 3/0 | 165 | 200 | 225 |
| 4/0 | 195 | 230 | 260 |
| 250 | 215 | 255 | 290 |
| 300 | 240 | 285 | 320 |
| 350 | 260 | 310 | 350 |
| 400 | 280 | 335 | 380 |
| 500 | 320 | 380 | 430 |
| 600 | 350 | 420 | 475 |
| 750 | 400 | 475 | 535 |
| 1000 | 455 | 545 | 615 |
Not more than three current-carrying conductors in a raceway or cable, 30°C ambient. Amperes.
| Size | 60°C | 75°C | 90°C |
|---|---|---|---|
| 14 | — | — | — |
| 12 | 15 | 20 | 25 |
| 10 | 25 | 30 | 35 |
| 8 | 30 | 40 | 45 |
| 6 | 40 | 50 | 55 |
| 4 | 55 | 65 | 75 |
| 3 | 65 | 75 | 85 |
| 2 | 75 | 90 | 100 |
| 1 | 85 | 100 | 115 |
| 1/0 | 100 | 120 | 135 |
| 2/0 | 115 | 135 | 150 |
| 3/0 | 130 | 155 | 175 |
| 4/0 | 150 | 180 | 205 |
| 250 | 170 | 205 | 230 |
| 300 | 195 | 230 | 260 |
| 350 | 210 | 250 | 280 |
| 400 | 225 | 270 | 305 |
| 500 | 260 | 310 | 350 |
| 600 | 285 | 340 | 385 |
| 750 | 320 | 385 | 435 |
| 1000 | 375 | 445 | 500 |
Same basis as the copper table. Small aluminum conductors are uncommon below 12 AWG.
| Ambient temperature | 60°C | 75°C | 90°C |
|---|---|---|---|
| 21–25°C (70–77°F) | 1.08 | 1.05 | 1.04 |
| 26–30°C (78–86°F) | 1.00 | 1.00 | 1.00 |
| 31–35°C (87–95°F) | 0.91 | 0.94 | 0.96 |
| 36–40°C (96–104°F) | 0.82 | 0.88 | 0.91 |
| 41–45°C (105–113°F) | 0.71 | 0.82 | 0.87 |
| 46–50°C (114–122°F) | 0.58 | 0.75 | 0.82 |
| 51–55°C (123–131°F) | 0.41 | 0.67 | 0.76 |
| 56–60°C (132–140°F) | — | 0.58 | 0.71 |
| 61–65°C (141–149°F) | — | 0.47 | 0.65 |
| 66–70°C (150–158°F) | — | 0.33 | 0.58 |
| 71–75°C (159–167°F) | — | — | 0.50 |
| 76–80°C (168–176°F) | — | — | 0.41 |
Multiply the table ampacity by the factor for the ambient temperature the conductor will actually see.
| Current-carrying conductors | Percent of table value | Multiplier |
|---|---|---|
| 4 to 6 | 80% | 0.80 |
| 7 to 9 | 70% | 0.70 |
| 10 to 20 | 50% | 0.50 |
| 21 to 30 | 45% | 0.45 |
| 31 to 40 | 40% | 0.40 |
| 41 and above | 35% | 0.35 |
Apply after temperature correction whenever more than three current-carrying conductors share a raceway or cable.
| Size | Circular mils |
|---|---|
| 14 | 4,107 |
| 12 | 6,530 |
| 10 | 10,380 |
| 8 | 16,510 |
| 6 | 26,240 |
| 4 | 41,740 |
| 3 | 52,620 |
| 2 | 66,360 |
| 1 | 83,690 |
| 1/0 | 105,600 |
| 2/0 | 133,100 |
| 3/0 | 167,800 |
| 4/0 | 211,600 |
| 250 | 250,000 |
| 300 | 300,000 |
| 350 | 350,000 |
| 400 | 400,000 |
| 500 | 500,000 |
| 600 | — |
| 750 | — |
| 1000 | — |
Used for voltage drop, resistance, and conductor area calculations.
Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.
Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.