Wiring Methods

Support spacing, burial depths, offset multipliers, 90° deducts, and bend radius.

Support spacing

Chapter 3, Articles 320 to 362
Wiring methodSupport requirementNEC
EMTEvery 10 ft, and within 3 ft of each box or fitting358.30
IMCEvery 10 ft, and within 3 ft of each box or fitting342.30
RMCEvery 10 ft, and within 3 ft of each box or fitting344.30
Rigid PVCEvery 3 ft, and within 3 ft of each box or fitting352.30
ENTEvery 3 ft, and within 3 ft of each box or fitting362.30
NM cable (Romex)Every 4.5 ft, and within 12 in of each box334.30
AC / MC cableEvery 6 ft, and within 12 in of each box330.30, 320.30
LFMC / LFNCSecured within 12 in of each box; support at 3 ft where unsupported runs are allowed350.30, 356.30
FMCSecured within 12 in of each box; supported at 4.5 ft intervals348.30

Minimum burial depth

300.5
InstallationMinimum coverNEC
Direct-buried cables or conductors24 in300.5
RMC or IMC6 in300.5
Rigid PVC, general18 in300.5
Under streets, roads, alleys, driveways, parking lots24 in300.5
One- and two-family dwelling driveways and yards18 in300.5
Residential 120 V branch circuit, 20 A or less, GFCI protected12 in300.5

Cover is measured from the top of the raceway or cable to the finished grade. Local amendments and utility requirements can exceed these depths.

Offset multipliers

Bend angleMultiplierShrink per inch of rise
10°6.01/16" per inch of rise
22.5°2.63/16" per inch of rise
30°2.01/4" per inch of rise
45°1.413/8" per inch of rise
60°1.151/2" per inch of rise

Multiply the offset rise by the multiplier to get the distance between bends. Add the shrink so the run finishes at the right length.

Stub 90s and bend radius

358.24
Trade size90° deductMinimum bend radius
1/2" EMT5 in4 in
3/4" EMT6 in4-1/2 in
1" EMT8 in5-3/4 in
1-1/4" EMT11 in7-1/4 in
1-1/2" EMT14 in8-1/4 in
2" EMT16 in9-1/2 in

Deduct figures are typical for a hand bender. Always verify against the bender shoe you are using.

Installation limits

  • No more than 360° of total bends between pull points, including offsets and kicks.
  • Power raceways may not be smaller than 1/2 in. trade size.
  • Every raceway needs a box or fitting at each end, and the box must be accessible.
  • Use expansion fittings wherever a raceway crosses a building expansion joint.
  • Cut threads on RMC and IMC and use listed fittings; keep the raceway electrically continuous for grounding.
  • Support within 3 ft of a box does not replace supporting the run itself.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.