The tables, formulas, and code limits electricians reach for every day — organized by topic.
REFERENCE TOPIC
Support spacing, burial depths, offset multipliers, 90° deducts, and bend radius.
| Wiring method | Support requirement | NEC |
|---|---|---|
| EMT | Every 10 ft, and within 3 ft of each box or fitting | 358.30 |
| IMC | Every 10 ft, and within 3 ft of each box or fitting | 342.30 |
| RMC | Every 10 ft, and within 3 ft of each box or fitting | 344.30 |
| Rigid PVC | Every 3 ft, and within 3 ft of each box or fitting | 352.30 |
| ENT | Every 3 ft, and within 3 ft of each box or fitting | 362.30 |
| NM cable (Romex) | Every 4.5 ft, and within 12 in of each box | 334.30 |
| AC / MC cable | Every 6 ft, and within 12 in of each box | 330.30, 320.30 |
| LFMC / LFNC | Secured within 12 in of each box; support at 3 ft where unsupported runs are allowed | 350.30, 356.30 |
| FMC | Secured within 12 in of each box; supported at 4.5 ft intervals | 348.30 |
| Installation | Minimum cover | NEC |
|---|---|---|
| Direct-buried cables or conductors | 24 in | 300.5 |
| RMC or IMC | 6 in | 300.5 |
| Rigid PVC, general | 18 in | 300.5 |
| Under streets, roads, alleys, driveways, parking lots | 24 in | 300.5 |
| One- and two-family dwelling driveways and yards | 18 in | 300.5 |
| Residential 120 V branch circuit, 20 A or less, GFCI protected | 12 in | 300.5 |
Cover is measured from the top of the raceway or cable to the finished grade. Local amendments and utility requirements can exceed these depths.
| Bend angle | Multiplier | Shrink per inch of rise |
|---|---|---|
| 10° | 6.0 | 1/16" per inch of rise |
| 22.5° | 2.6 | 3/16" per inch of rise |
| 30° | 2.0 | 1/4" per inch of rise |
| 45° | 1.41 | 3/8" per inch of rise |
| 60° | 1.15 | 1/2" per inch of rise |
Multiply the offset rise by the multiplier to get the distance between bends. Add the shrink so the run finishes at the right length.
| Trade size | 90° deduct | Minimum bend radius |
|---|---|---|
| 1/2" EMT | 5 in | 4 in |
| 3/4" EMT | 6 in | 4-1/2 in |
| 1" EMT | 8 in | 5-3/4 in |
| 1-1/4" EMT | 11 in | 7-1/4 in |
| 1-1/2" EMT | 14 in | 8-1/4 in |
| 2" EMT | 16 in | 9-1/2 in |
Deduct figures are typical for a hand bender. Always verify against the bender shoe you are using.
Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.
Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.