The tables, formulas, and code limits electricians reach for every day — organized by topic.
REFERENCE TOPIC
Offset bend geometry, box fill counting, series and parallel circuits, and schematic symbols.
Ten bends cover essentially every run you will make in EMT. Learn the layout for each one and the size of the conduit stops mattering.
90° stub-up
Take a run up a wall into a box, panel, or disconnect.
Back-to-back 90s
Two 90s facing the same way, the span between the backs set by a panel or box spacing.
Offset (two-bend)
Step a run up or down to clear an obstruction, then continue parallel to itself.
Four-point saddle
Hop over a pipe, coupling, or beam with equal legs on both sides of the obstruction.
Three-point saddle
A quick V over a single round obstruction where a wide saddle is not needed.
Kick 90
A 90 that also has to move sideways to line up with an offset box or panel entry.
Parallel offsets
A rack of conduits that step together and stay evenly spaced.
Angle bend
Turn a run by a fixed angle — 30°, 45°, 60° — without a second bend.
Concentric bends
Several 90s sharing one center, nested inside each other into a panel or gutter.
Segment (multi-shot) bend
A large-radius sweep too big for a one-shot pull, bent in equal increments.
Every bend below is bent on the same bender — what changes is the layout: where the marks go, which bender mark they sit on, and which direction each pull faces.
Take-up changes with trade size and bender, so the stub mark is measured length minus take-up. Match the bender to the size before you mark anything.
| EMT trade size | Bender | Take-up (deduct) | 90° stub mark | Field note |
|---|---|---|---|---|
| ½" | Hand bender | 5" | length − 5" | One-shot 90s; the size most offsets and saddles are laid out on. |
| ¾" | Hand bender | 6" | length − 6" | Same technique as ½", a longer handle pull. |
| 1" | Hand bender or mechanical | 8" | length − 8" | Two hands on the handle; keep the heel planted. |
| 1¼" | Mechanical or hydraulic | 11" | length − 11" | Check the shoe chart — most hand benders stop at 1". |
| 1½" | Mechanical or hydraulic | 14" | length − 14" | Support the run while the shoe comes up to angle. |
| 2" | Mechanical or hydraulic | 16" | length − 16" | Sweep 90s if the radius allows; otherwise segment-bend. |
Take-up belongs to the bender, not the conduit. Confirm the number stamped on your bender or its chart before the first mark of a job — a wrong take-up is a wrong stub every time.
BENDER MARKS
The same ten steps work on a service rack, a classroom bender, or a panel change in a basement.
Lay out the whole run first
Measure the complete path — every obstruction, box entry, and turn — before anything is cut. Bends are easy; guesswork is not recoverable.
Add the shrink before you cut
Every offset shortens the run by rise × shrink. Add it back into the measured length so the last bend still lands on the box.
Cut long, trim after
You can always cut a stub shorter. There is no way to stretch one that came up 2 inches short.
Mark on the bender side
Mark with a pencil or marker on the same face of the conduit that meets the bender's arrow, so the mark stays visible while you load it.
Match bender to size
Every shoe is built for one trade size and wall type. Never force a conduit into the wrong bender — it crushes the wall and kinks at the elbow.
Load with the seam on the inside
The weld seam rides on the inside of the bend or the neutral axis. On the outside it stretches, splits, and snags the pull.
One steady pull
Heel planted on the floor, both hands on the handle, one continuous motion. Stopping mid-bend and restarting leaves a flat spot in the sweep.
Check, then correct for springback
Square, level, or protractor against the bend. Steel springs back a degree or two, so above 45° pull slightly past the mark and let it relax.
Dry-fit before installing
Bends in the wrong plane cannot be undone without cutting. Lay the assembly out on the floor against the layout and check every plane.
Support it like straight conduit
Secured within 3 ft of every box and every 10 ft on the run (358.30) — a bend is not a support.
WHAT GOES WRONG
Support and bend limits: no more than 360° of bend between pull points (358.26), supported within 3 ft of every box and every 10 ft on the run (358.30).
Lay out an offset with three numbers: the rise, the multiplier for the angle, and the shrink.
| Bend angle | Multiplier | Shrink per inch of rise | Where it is used |
|---|---|---|---|
| 10° | 5.76 (round to 6.0) | 1/16" | Long, shallow step over a minor obstruction. |
| 22.5° | 2.61 | 3/16" | Half of a 45° saddle; tight quarters. |
| 30° | 2.00 | 1/4" | The everyday offset — easy to pull, easy to check. |
| 45° | 1.41 | 3/8" | Short offset, and the outer bends of a four-point saddle. |
| 60° | 1.15 | 1/2" | Only where space forces it — watch the 360° total. |
Every item in the box gets a volume allowance. Add them, compare to the box volume, done.
| Symbol | Meaning | Where it shows up |
|---|---|---|
| ─o─ | Single-pole switch | Controls one load from one location |
| ─o=o─ | Three-way switch | Controls one load from two locations |
| ─o×o─ | Four-way switch | Between two three-ways for three or more locations |
| ⌾ | Duplex receptacle | General-purpose outlet |
| ◍ | GFCI receptacle | Wet, outdoor, and kitchen locations |
| ⌽ | Luminaire | Lighting outlet |
| ⏚ | Ground | Equipment grounding conductor termination |
| ⊣⊢ | Capacitor | Motor starting and power factor correction |
| M | Motor | Any motor-driven load |
| T | Transformer | Voltage change, separately derived systems |
Drawn conventions used on plans and ladder diagrams, not a code requirement.
Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.
Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.