Pocket Reference

The tables, formulas, and code limits electricians reach for every day — organized by topic.

REFERENCE TOPIC

Devices & Receptacles

NEMA configurations, GFCI and AFCI locations, spacing rules, and mounting heights.

NEMA receptacle configurations

ConfigurationVoltageRatingTypical use
5-15R125 V15 AStandard household duplex
5-20R125 V20 AKitchen, laundry, garage; T-slot accepts both
6-15R250 V15 A250 V equipment, small compressors
6-20R250 V20 AAir conditioners, welders, shop equipment
6-30R250 V30 AOlder 3-wire dryer and water heater connections
6-50R250 V50 AWelders, older ranges, EV chargers
10-30R125/250 V30 AOlder 3-wire dryer (no neutral ground)
14-30R125/250 V30 ACurrent 4-wire dryer
14-50R125/250 V50 ARanges, RVs, EV chargers
14-60R125/250 V60 ALarge ranges and shop equipment
TT-30R125 V30 ATravel trailer and campground pedestal
L5-20R125 V20 ATwist-lock, cord-connected equipment
L6-30R250 V30 ATwist-lock, compressors and machinery
L14-30R125/250 V30 AGenerator inlet and transfer switch

The first number is the configuration family, the letter is R for receptacle or P for plug. Matching voltage and amperage is what keeps the wrong cord out of the wrong outlet.

Where GFCI protection is required

210.8(A)
  • Bathrooms
  • Garages and accessory buildings with a floor at or below grade
  • Outdoors
  • Crawl spaces at or below grade
  • Unfinished basements
  • Kitchen countertop surfaces
  • Receptacles within 6 ft of a sink (laundry, utility, wet bar)
  • Laundry areas
  • Bathtub and shower spaces
  • Boathouses
  • Indoor wet-bar sinks

All 125 V through 250 V receptacles in these dwelling-unit locations. Check your state's adopted edition, since the list has grown over time.

Where AFCI protection is required

210.12
  • Kitchens and dining rooms
  • Family rooms, living rooms, parlors, libraries, dens
  • Bedrooms and closets
  • Hallways and stairways
  • Laundry areas
  • Sunrooms and recreation rooms
  • Any similar room or area in a dwelling unit

All 120 V, single-phase, 15 A and 20 A branch circuits supplying outlets in these dwelling-unit rooms.

Receptacle placement and circuit rules

  • Wall spaces 2 ft or wider need a receptacle, and no point along the floor line may be more than 6 ft from one (210.52(A)).
  • Kitchen countertop spaces 12 in or wider need a receptacle, and no point may be more than 24 in from one (210.52(C)(1)).
  • Countertop receptacles may not be more than 20 in above the countertop.
  • At least one receptacle at the front and back of a dwelling, plus one in an attached garage (210.52(E), (G)).
  • Hallways 10 ft or longer need at least one receptacle (210.52(H)).
  • A bathroom needs at least one receptacle on a dedicated 20 A circuit (210.11(C)(3), 210.52(D)).
  • A kitchen needs two or more 20 A small-appliance branch circuits (210.11(C)(1)).
  • A laundry area needs a dedicated 20 A circuit and at least one receptacle (210.11(C)(2), 210.52(F)).

Common mounting heights

DeviceHeight AFFNote
General receptacle (bottom of box)12–18 inCommon practice; code sets no general minimum
Switch (center of box)48 inMatches typical door hardware
Kitchen countertop receptacle42–48 inAbove backsplash, below uppers, max 20 in over counter
Bathroom vanity receptacle42–48 inKeep clear of the sink basin
Dryer receptacle36–42 inAbove and behind the appliance
Range receptacle6–12 inLow, behind the appliance
Panel working space headroom78 in minCode requirement (110.26(A)(3))

Field practice, not a code minimum, unless the NEC column says otherwise.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.