The tables, formulas, and code limits electricians reach for every day — organized by topic.
REFERENCE TOPIC
Approach boundaries, arc-rated PPE, glove classes, and the lockout / tagout sequence.
| Voltage (AC) | Limited approach | Restricted approach |
|---|---|---|
| 50 to 300 V | 10 ft 0 in | Avoid contact |
| 301 to 750 V | 10 ft 0 in | 1 ft 0 in |
| 751 V to 15 kV | 10 ft 0 in | 1 ft 5 in |
| 15.1 to 36 kV | 10 ft 0 in | 2 ft 4 in |
| 36.1 to 46 kV | 10 ft 0 in | 2 ft 9 in |
Unqualified persons stay outside the limited approach boundary. Only qualified workers wearing the correct PPE cross it.
| Incident energy | PPE category | Minimum arc rating |
|---|---|---|
| 1.2 cal/cm² or less | No arc-rated PPE required | — |
| 1.2 to 4 cal/cm² | Category 1 | 4 cal/cm² |
| 4 to 8 cal/cm² | Category 2 | 8 cal/cm² |
| 8 to 25 cal/cm² | Category 3 | 25 cal/cm² |
| 25 to 40 cal/cm² | Category 4 | 40 cal/cm² |
PPE categories are a shorthand for the arc rating the clothing, face protection, and gloves must provide. Always use the arc flash study for the equipment you are working on.
| Glove class | Maximum use voltage |
|---|---|
| Class 00 | 500 V AC |
| Class 0 | 1,000 V AC |
| Class 1 | 7,500 V AC |
| Class 2 | 17,000 V AC |
| Class 3 | 26,500 V AC |
| Class 4 | 36,000 V AC |
| # | Step | What it means in the field |
|---|---|---|
| 1 | Prepare | Identify all energy sources, review the procedure, and assemble locks, tags, and test instruments. |
| 2 | Notify | Tell all affected workers that the equipment is being shut down and locked out. |
| 3 | Shut down | Use the normal stopping procedure. Never pull a disconnect under load unless it is rated for it. |
| 4 | Isolate | Open every disconnecting means that feeds the equipment, including control and stored-energy sources. |
| 5 | Lock and tag | Apply a personal lock and tag to each isolation point. One lock and key per qualified worker. |
| 6 | Release stored energy | Bleed capacitors, block or relieve springs, release pressure, and ground where required. |
| 7 | Verify | Test for absence of voltage with a meter proven on a known live source before and after the test. |
| 8 | Restore | Confirm the work is complete and the area clear, remove locks and tags in reverse order, then re-energize. |
Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.
Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.