Pocket Reference

The tables, formulas, and code limits electricians reach for every day — organized by topic.

REFERENCE TOPIC

Arc Flash & Safety

Approach boundaries, arc-rated PPE, glove classes, and the lockout / tagout sequence.

Shock approach boundaries

NFPA 70E 130.4
Voltage (AC)Limited approachRestricted approach
50 to 300 V10 ft 0 inAvoid contact
301 to 750 V10 ft 0 in1 ft 0 in
751 V to 15 kV10 ft 0 in1 ft 5 in
15.1 to 36 kV10 ft 0 in2 ft 4 in
36.1 to 46 kV10 ft 0 in2 ft 9 in

Unqualified persons stay outside the limited approach boundary. Only qualified workers wearing the correct PPE cross it.

Arc-rated PPE by incident energy

Incident energyPPE categoryMinimum arc rating
1.2 cal/cm² or lessNo arc-rated PPE required—
1.2 to 4 cal/cm²Category 14 cal/cm²
4 to 8 cal/cm²Category 28 cal/cm²
8 to 25 cal/cm²Category 325 cal/cm²
25 to 40 cal/cm²Category 440 cal/cm²

PPE categories are a shorthand for the arc rating the clothing, face protection, and gloves must provide. Always use the arc flash study for the equipment you are working on.

Rubber insulating glove classes

ASTM D120
Glove classMaximum use voltage
Class 00500 V AC
Class 01,000 V AC
Class 17,500 V AC
Class 217,000 V AC
Class 326,500 V AC
Class 436,000 V AC

Lockout / tagout sequence

NFPA 70E 120.2
#StepWhat it means in the field
1PrepareIdentify all energy sources, review the procedure, and assemble locks, tags, and test instruments.
2NotifyTell all affected workers that the equipment is being shut down and locked out.
3Shut downUse the normal stopping procedure. Never pull a disconnect under load unless it is rated for it.
4IsolateOpen every disconnecting means that feeds the equipment, including control and stored-energy sources.
5Lock and tagApply a personal lock and tag to each isolation point. One lock and key per qualified worker.
6Release stored energyBleed capacitors, block or relieve springs, release pressure, and ground where required.
7VerifyTest for absence of voltage with a meter proven on a known live source before and after the test.
8RestoreConfirm the work is complete and the area clear, remove locks and tags in reverse order, then re-energize.

Non-negotiables

  • De-energize first. Energized work requires a documented justification, an energized work permit, and an arc flash risk assessment.
  • Test before touch, and prove the meter on a known live source before and after the test.
  • Wear the correct arc rating for the task, including face and hand protection, every time you cross the restricted boundary.
  • Verify glove and sleeve test dates before each use; retest on the interval required by your program.
  • Treat every conductor as energized until it has been tested, locked, and grounded where required.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.